Signal Conditioners, Temperature Transmitters and Controllers
Modbus RTU, Modbus TCP, Canbus, PLC's and Hmi's.
Call toll Free 1 887 877 4to 20mA or 1 877 486 2062
  • 4 Digit Temperature Controller ATR142.
  • ATR142 FEATURES

    • UL, CE.
    • Ramp and Soak Generator
    • Set point Display
    • Digital Input
    • PC Programmable
    • Memory Card Programmable
    • 1 1/4 x 2 7/8 " cut out
    • 32 X 74 MM cut out
    • Isolated
    • Output up to 2 Relays
    • SSR
    • Option Modbus

Ramp Soak Temperature Controller, ATR142

General Description

The ATR142 Ramp generator and Soak Temperature Controller is a 4 digit PID controller with a local display for the measured variable and the set point.
The ATR142 can have 3 set points. Which can be triggered by a digital input. The 3 set points can be used to build a temperature profile that drives the temperature up and down at predetermined intervals. Also the temperature can be maintained for a period of time and then cooled down at a predetermine time period.
The ATR142 can have up to 2 relays, a Solid State Output and an option to have a Modbus RS485 output. The ATR142 is only 1 1/4 x 2 7/8" cut out and is able to withstand environmental conditions up to IP65 with the optional gasket.
The ATR142 can be programmed with the front panel keypad or PC based software and multiple units can be cloned with the use of a memory card enabling high speed configuration. The PC based software can also be used to monitor several Temperature Controllers.
The ATR142 has various sensor inputs including Thermocouples, RTD's, mA, Voltage, mV, Thermistors and Potentiometers. Desired control is maintained with PID and auto tuning.

INPUT
Thermocouple
RTD's
mA
Volts and mV
Thermistor
Potentiometer
OUTPUT
2 x Relays
SSR
Option Modbus.

POWER SUPPLY
Power Supply Voltage 12...24VAC or Vdc
24/115/230VAC
POWER CONSUMPTION
4.6VA MAX
CONFIGURATION
Front panel Keyboard
PC Configurable.
Memory Card.
ISOLATION
Yes.
EMC
For Industrial environments
Immunity EN 61000-6-2
Emission EN 6100-6-4
HOUSING
Material self-extinguishing
Dimensions W x H x T
3" x 1 3/8 " x 2 1/8"
35 x 77x x 53 mm
Weight 3 oz 100 g
TEMPERATURE
Operating Temperature 32°F +113°F 0°C +45°C
Humidity (non condensing) 35-95%

 

Specifications

Input °F °C
K Type Thermocouple -436 to 2480°F -260 to 1360°C
S Type Thermocouple -40 to 3200°F -20 to 1760°C
R Type Thermocouple -40 to 3200°F -20 to 1760°C
J Type Thermocouple -328 to 3200°F -200 to 1760°C
RTD PT100 -328 to 1112°F -200 to 600°C
RTD PT100 -328 to 284°F -200 to 140°C
NI 100 -76 to 356°F -60 to 180°C
NTC 10K Ohm Thermistor -40 to 257°F -40 to 125°C
PTC 1K Ohm Thermistor -40 to 302°F -40 to 150°C
PT500 -148 to 1112°F -100 to 600°C
PT1000 -148 to 1112°F -100 to 600°C
Voltage 0 to 10V 0-40mV
Current 0 to 20mA 4 to 20mA
Potentiometer 1 to 6K 1 to 150K
Output: 2 X Relays 8 A. SSR.
Power Supply: 12 to 24Vac/Vdc, 115Vac, 230Vac.
Power Consumption: 3 to 6VA max.
Temperature rating: Operative- 32°F +113°F -0°C +45°C
Humidity: (non condensing) 35-95%.
Housing: Polycarbonate UL94V2 self-extinguishing
Dimensions: 3 3/8" x 3 " x 2 1/8", 35 x 77x x 53 mm.
Weight: 3 oz 100 g.
EMC. For industrial environments.
  Immunity: EN 61000-6-2.
  Emission: EN 61000-6-4.
Configuration: PC Configurable, Memory Card

Drawings

Power supply
Positive Terminal 2
Negative Terminal 1
Output  
Relay 1
Normally Closed Terminal 3
Common Terminal 4 
Normally Open Terminal 5
Relay 2
Common Terminal 6
Normally Open Terminal 7
RS485 Option Terminal 6 
Terminal 7
SSR Output Negative 8
Positive 9 
T/C's, Voltage, mA Positive 12
Negative 11
2 Wire Current Negative 9
Positive 12
Thermistor Terminal 10
Terminal 11
Potentiometer Terminal 10
Terminal 12
Wiper Terminal 11

ATR142-Wiring-Diagram

Applications

  • Ramp generation Temperature Control.
  • Environmental Chamber.
Back to General Description Ramp Soak Temperature Controller ATR142.