Signal Conditioners, Temperature Transmitters and Controllers
Modbus RTU, Modbus TCP, Canbus, PLC's and Hmi's.
Call toll Free 1 887 877 4to 20mA or 1 877 486 2062
  • 2000.35.013 Loop Powered Current converter
  • 2000.35.013 FEATURES

    • Loop Powered Current Transducer.
    • DIP Switch Programmable.
    • Input 0-25Amp.
    • Input 0-50Amp.
    • Output 2 wire 4-20mA.
    • DIN Rail Mounted.

Loop Powered Current converter

General Description

The 2000.35.013 is a Loop Powered Current transducer that provides a 2 wire 4-20mA loop powered output. It is designed to detect the TRMS value of the AC or DC current. It is DIP Switch selectable for either 0-25A, or 0-50A full scale. The resolution is 12 Bit with an accuracy of 0.5%.

The 3000 Vac isolation between input and the signal output eliminates the effects of all ground loops and allows the use of the converter in heavy environmental conditions found in industrial applications. The Current transformer can be mounted on a DIN Rail strip.

The Baud-rate and address can be set by DIP switches.

INPUT
Current 0-25 Amp, 0-50 Amp.
OUTPUT
2 Wire 4-20mA.
POWER SUPPLY
Power Supply Voltage 11-350DC
CURRENT CONSUMPTION
3.5 mA
CONFIGURATION
DIP Switch Configurable.
ISOLATION
Between Input and Output 3000Vac.
EMC
For Industrial environments
Immunity EN 61000-6-2
Emission EN 6100-6-4
HOUSING
Material self-extinguishing
Dimensions W x H x T
1.8" x 2.52 " x 1.1"
46 X 63 X 27mm
Weight 3 oz 90 g
TEMPERATURE
Operating Temperature 5°F +149°F -15°C +65°C
Storage Temperature -40°F +185°F-40°C +85°C
Humidity (non condensing) 0-90%

 

Specifications

Input: Current 0-25 Amp, 0-50 Amp
Output: 2 Wire 4-20mA
Power Supply: 11 to 30 Vdc.
Current Consumption: Current output 3.5 mA max.
Temperature rating: Operative 5°F +149°F - 15°C +65°C
  Temperature Storage Temperature - 40°F +185°F - 40°C +85°C.
Humidity: (non condensing) 0-90%.
Housing: Material Self-extinguishing.
Dimensions: 1.8" x 2.52 " x 1.1", 46 x 63 x 27 mm.
Weight: 3 oz 90 g.
EMC. For industrial environments.
  Immunity: EN 61000-6-2.
  Emission: EN 61000-6-4.
Configuration: DIP Switch Configurable

Drawings

Power Supply  
Positive Pin 1
Negative Pin 2

2000.35.013 wiring Diagram.


Applications

  • Loop Powered Current converter.
  • 0 to 25 Amps to 4-20mA.
  • 0 to 50 Amps to 4-20mA.
Back to General Description