Signal Conditioners, Temperature Transmitters and Controllers
Modbus RTU, Modbus TCP, Canbus, PLC's and Hmi's.
Call toll Free 1 887 877 4to 20mA or 1 877 486 2062
  • Thermocouple CANbus.
  • DAT7016 FEATURES

    • Thermocouple to CANopen.
    • mV to CANopen.
    • DIP Switch Configurable.
    • DiA DS and CiA DS 401 Compliance
    • DIN Rail Mounted.

CANopen Slave Device Thermocouple and mV input DAT7016

General Description

The DAT7016 accept inputs from up to 4 Thermocouples or mV. All standard types of thermocouples are acceptable. The analog signal is converted to 16 Bit data and Transmitter by the CANopen protocol.

The DAT7016 is compliant with CiA DS 301 and CiA DS 401 and can interface directly with the CAN Controllers that accept CiA DS 301 and CiA DS 401 Standards.

The Baud rate and the ID can be programmed by DIP switches positioned on the side of the enclosure. The Enclosure is DIN rail mounted and is 22.5 mm thick. The terminals are plug in so the device can be hot swapped. The DAT7016 is isolated up to 2000 Vac for 1 minute between the Input, CANopen network and the power supply.

INPUT
4 X Thermocouples and mV.
OUTPUT
CANopen.
POWER SUPPLY
Power Supply Voltage 10-30Vdc
Reverse polarity protection 60Vdc
CURRENT CONSUMPTION
45 mA
CONFIGURATION
DIP Switch Configurable.
ISOLATION
Between Input/Output/Power Supply 1500Vac.
EMC
For Industrial environments
Immunity EN 61000-6-2
Emission EN 6100-6-4
HOUSING
Material self-extinguishing
Dimensions W x H x T
3 1/2" x 4 1/2 " x 1/2"
90 x 112x x 12.5 mm
Weight 3 oz 90 g
TEMPERATURE
Operating Temperature -4°F +140°F -20°C +60°C
Storage Temperature -40°F +185°F-40°C +85°C
Humidity (non condensing) 0-90%

 

Specifications

Input: Thermocouple Type J, K, S, R, B, E, T, N and mV.
Output: CANopen
Power Supply: 10 to 30 Vdc. Reverse polarity protection 60 Vdc.
Current Consumption: Current output 35 mA max. Voltage output 25 mA max.
Temperature rating: Operative- 4°F +158°F - 20°C +70°C
  Temperature Storage Temperature - 40°F +185°F - 40°C +85°C.
Humidity: (non condensing) 0-90%.
Housing: Material Self-extinguishing.
Dimensions: 4" x 4 1/2 " x 1", 100 x 120x x 22.5 mm.
Weight: 3 oz 90 g.
EMC. For industrial environments.
  Immunity: EN 61000-6-2.
  Emission: EN 61000-6-4.
Configuration: PC Configurable and DIP Switch Configurable

Drawings

Input  
Thermocouple  
Channel 0 Terminal 2 and 3
Channel 1 Terminal 7 and 8
Channel 2 Terminal 12 and 14
Channel 3 Terminal L and N
Current mA  
Channel 0 Terminal 2 and 3
Channel 1 Terminal 7 and 8
Channel 2 Terminal 12 and 14
Channel 3 Terminal L and N
CAN Network Terminal D and F Ground E
Power Supply Positive B Negative A

CANbus Thermocouple wiring Diagram.


Applications

  • 4 Channel CANopen slave for Thermocouples.
  • 4 Channel CANopen slave for K Type Thermocouple.
  • 4 Channel CANopen slave for mV.
Back to General Description