All Way Signal Isolation Converter.

DAT4235

DAT4235 All Way Signal Isolation Converter.
All Way Signal Isolation Converter DAT4235.
• Universal input Isolated Signal converter.
• Input Thermocouples, RTD's, Potentiometers, Resistance and mV.
• PC Programmable Micro USB.
• All Way Isolation.
• DIN Rail Mounted.
• Output damping.
• LED power Indication.
General Description

The DAT4235 is an All-Way Signal Isolation Converter with the input, output, and power supply all isolated from each other. The DAT4235 is DIN Rail mount and PC programmable. Having a thickness of only 1/2" allows compact installation on either top hat DIN Rail or G type DIN Rail. The input is universal and selectable from thermocouples, RTD, mA, V, mV, resistance, and potentiometer. The DAT4235 is bipolar input and can accept negative inputs such as -20mA or -10V. For thermocouple inputs, the DAT4235 will linearize the input and provide a 4-20mA or voltage output signal. The DAT4235 is accurate to 0.1% full scale and has less than 0.01%/°f thermal drift.
The DAT4235 is programmable by Prosoft software version 3.06 PC based software, which has been developed by DATEXEL to be user friendly. The software can be downloaded free of charge on the download page at www.datexel.com.
For resistance and RTD sensors, it is possible to program the DAT4235 for 2, 3 or 4 wire RTD's.
It is possible to set the minimum and maximum values of the input and output ranges at any point of the scale, keeping the minimum span shown in the Data Sheet. Also, high burn out alarm or low burn out alarm is selectable.
The DAT4235 is isolated between the input, output, and power supply to 1500V, eliminating the effects of any ground loops, and allows the use of the converter in heavy environmental conditions found in industrial applications. The DAT4235 is in compliance with the standard 89/336/CEE on the Electromagnetic Compatibility.
The DAT4235 is housed in a plastic enclosure of 1/2", 12.5 mm thickness suitable for DIN rail mounting in compliance with EN-50022 and EN-50035 standards.
The DAT4235 is able to measure and linearize the standard thermocouples with internal cold junction compensation.
The DAT4235SEL is a version that allows the output signal to be enabled and disabled when a voltage is applied to the SEL terminals. The output is disabled and goes to a high impedance when the SEL input is energized by 4 to 30 Vdc. This allows several DAT4235SEL to be mounted together and used as a Multiplexer.

INPUT OUTPUT POWER SUPPLY
Current, Thermocouples, RTD, Voltage, Current 4-20mA, 0-20mA, 20-0mA Power Supply Voltage 18-32Vdc
Potentiometer, Resistance. Voltage 0-10V, 10-0V. Reverse polarity protection 60Vdc
CURRENT CONSUMPTION CONFIGURATION ISOLATION
Between 35 and 55 mA PC Programmable Between Input/Comms/Power Supply 1500Vac.
EMC HOUSING TEMPERATURE
For Industrial environments Material self-extinguishing Operating Temperature -40°F +185°F -40°C +85°C
Immunity EN 61000-6-2 Dimensions W x H x T 4 2/5 x 3 1/2" x 1/2" Storage Temperature -40°F +185°F-40°C +85°C
Emission EN 6100-6-4 112 x 90x x 12.5 mm Humidity (non condensing) 0-90%
Weight 3 oz 90 g

Specifications
Input type: Min  Max  Min. span 
K Type Thermocouple -328℉ 2500℉ 122℉
-200℃ 1370℃ 50℃
J Type Thermocouple -328℉ 2192℉ 122℉
-200℃ 1200℃ 50℃
R Type Thermocouple -58℉ 3200℉ 752℉
50℃ 1760℃ 400℃
S Type Thermocouple -58℉ 3200℉ 752℉
50℃ 1760℃ 400℃
B Type Thermocouple 752℉ 3308℉ 752℉
400℃ 1820℃ 400℃
E Type Thermocouple -328℉ 3308℉ 122℉
-200℃ 1000℃ 50℃
T Type Thermocouple -328℉ 752℉ 122℉
-200℃ 400℃ 50℃
N Type Thermocouple -328℉ 2372℉ 122℉
-200℃ 1300℃ 50℃
RTD 2,3,4 wires      
Pt100 -328℉ 1562℉ 68℉
-200℃ 200℃ 20℃
Pt1000 -328℉ 392℉ 122℉
-200℃ 200℃ 50℃
Ni100 -76℉ 356℉ 68℉
-60℃ 180℃ 20℃
Ni1000 -76℉ 302℉ 122℉
-60℃ 150℃ 50℃
Voltage
mV -400mV 400mV 2 mV
mV -100mV 700mV 2 mV
Volts -10V 10V 500mV
Potentiometer
Nominal value 200Ω 10%
200Ω 500Ω 10%
0.5KΩ 50KΩ 10%
RES. 2,3,4 wires
Low 300Ω 10Ω
High 2000Ω 10Ω
Current
mA -20mA 20mA 2mA
Output type Min Max Min. span
Direct current 4 mA 20 mA 4 mA
Reverse current 20 mA 4 mA 4 mA
Direct voltage 0 V 10 V 1 V
Reverse voltage 10 V 0 V 1 V
Input calibration  
RTD > of ±0.1% f.s. or ±0.36 ℉ ±0.2 ℃
Low res. > of ±0.1% f.s. or ±0.27 ℉ ±0.15℃
High res. > of ±0.2% f.s. or ±1 Ω
mV, T/C > of ±0.1% f.s. or ±18 uV
Volts > of ±0.1% f.s. or ±2 mV
mA > of ±0.1% f.s. or ±6 uA
Output Calibration
Current ±7 uV
Voltage ±5 mV
Input impedance
T/C, mV <=10MΩ
Volts <=1MΩ
Current ~ 50Ω
Linearity (1)
T/C ± 0.2 % f.s.
RTD ± 0.1 % f.s.
Line resistance influence
T/C mV <=0.8uV/Ω
RTD 3 wires 0.05%/Ω 50Ω (balanced max)
RTD 4 wires 0.005%/Ω 100Ω (balanced max)
RTD excitation current
Typical 0.35mA
Thermal drift (1)  
Full scale ±0.018 ℉ ±0.01% ℃
CJC ±0.018 ℉ ±0.01% ℃
Response time (10÷ 90%) about 50 ms
Burn-out values  
Max Current Output value 21.5mA
Min Current Output value -21.5mA
Max Voltage Output value 10.5 V
Min Voltage Output value -10.5 V
Damping time constant  
Selectable from 0.1 to 30 s.
Value 0 function not active.
Power supply
Power supply voltage 10 .. 32 Vdc
Reverse polarity protection 60 Vdc max
Current Consumption
Current Output 55 mA
Voltage Output 35 mA
Output Load resistance
Current output Rload >650Ω
Voltage output Rload <600Ω
Between Input, Output and Power supply 1500 Vac, 50Hz, 1 Min
Temperature & humidity
Operative temperature -40℉ to 185℉
-40℃ to 85℃
Storage temperature -40℉ to 185℉
-40℃ to 85℃
Humidity (not condensed) 0 to 90 %
Maximum Altitude 2000m
Installation Indoor
Category of installation II
Pollution Degree 2
Housing
Material Self-extinguishing plastic
IP Code IP20
Wiring 0.8 to 2.1 mm2 AWG14-18
Tightening Torque 0.8 N m
Mounting DIN Rail EN-50022 and EN-50035
Weight 3 Oz
90 g.
Dimensions W 0.5" H 3" D 4.4"
W 12.5mm H 90mm D 112mm
EMC for industrial environments
Immunity EN 61000-6-2
Emission EN 61000-6-4
Drawings

DAT4235: CONFIGURATION

Notice: Before programming, check that the drivers have previously been installed on the Personal Computer.
1) Open the protective plastic cover to access the Micro USB connection on DAT4235.
2) Connect the two plugs of cable CVPROG to the Personal Computer (USB plug) and to the device (uUSB plug).
3) Run the software PROSOFT. Set the COM port assigned to the CVPROG cable by the Operative System.
4) Set the parameters of configuration.
5) Program the device.

CONFIGURATION BY CABLE CVPROG

Notice, during this operation don't power on the device. How to program a Head Mounted Temperature Transmitter

DAT4235: INSTALLATION INSTRUCTIONS

The DAT4235 is suitable for DIN rail mounting with EN-50022 Top Hat and EN-50035 G Section rails.

DAT4235 ISOLATION STRUCTURE

The input and output are isolated from each other and the power supply.

isolation structure of the Dat4235
Thermocouple Input
Thermocouple Input  
Thermocouple Terminals + L and - I
Thermocouple input connections for Dat4235
mV Input
mV Input
mV Terminals + L and - I
millivolt input connections for Dat4235
2 Wire RTD Input
2 Wire RTD and 2 Wire Resistance Input
2 Wire RTD Terminals G and I
2 Wire Resistance Terminals G and I
2 wire Resistance input connections for Dat4235
3 Wire RTD Input
3 Wire RTD and 3 Wire Resistance Input
3 Wire RTD Terminals G,H and I
3 Wire Resistance Terminals G,H and I
3 wire Resistance input connections for Dat4235
4 Wire RTD Input
4 Wire RTD and 4 Wire Resistance Input
4 Wire RTD Terminals G,H and L,I
4 Wire Resistance Terminals G,H and L,I
4 Wire RTD input connections for Dat4235
Potentiometer Input
4 Wire RTD Terminals G,I and wiper H
potentiometer input connections for Dat4235
Voltage Input
Volts Terminals + E and - I
Voltage input connections for Dat4235
Passive mA Input
Passive mA Input  
mA input connections for Dat4235
DAT4235: Power Supply Connections
18 to 30 Vdc power supply  
Power Supply Terminals + Q and - R
Power Supply for DAT4235
DAT4235: Output Signals
Voltage Output  
Signal Terminals + N and - M
Voltage signal output for DAT4235
Current Output  
Signal Terminals + N and - M
Current signal output for DAT4235
DAT4235: Damping Function
Damping Function of the DAT4235
DAT4235: Dimensions
DAT4235 dimensions

The DAT4235 is provided as requested on the Customer's order. Refer to the section “Technical specification” to determine input and output ranges. The mounting kit for DIN rail is provided only on request with code DIN RAIL. In case the configuration is not specified, the parameters must be set by the user.

DAT4235: Dimensions
DAT4235 Pt1003 Wires0-200℉ S.L.4-20mA Burn-out up
Column 1 Product Name DAT4235
Column 2 Input type mA, Volts, RTD, Resistance, mV, or Pot
Column 3 Sensor option RTD/Res 2, 3, or 4 wire
Column 4 Input range Zero and span setting
Column 5 linearization linearization options
S.L. Standard linearization
N.L. No linearization
C.L. linearization by step Custom: specify input curve
Column 6 Burn out up Burnt output option High or Lo
LED Signal Indication

The DAT4235 has an LED on the front panel for status indication.

LEDColorStateDescription
PowerGreenOnDevice has power
OffDevice has no power
Applications

DAT4235 Custom made products.

What is a DAT 4235 31108?
The DAT4235 31108 is a special version with input Range ± 250 mA.
What is a DAT 4235 190614?
The DAT4235 190614 is designed with an input for ± 15 Vdc.
What is a DAT 4235 40220?
The DAT4235 40220 has an input for PTC RE 95180 Bosch thermistor with a range -40°C/+150°C.
What is a DAT 4235 111220?
The DAT4235 111220 has an input for an NTC PTM51F thermistor with a range of 0 to 200 °C and a fixed output of 0-10 V.
What is a DAT 4235 40221?
The DAT4235 40221 has an input for an NTC 10k thermistor RL0503 10-150°C output 0-10 V.
What is a DAT 4235 110221?
The DAT4235 110221 has an input for an NTC5k Noris Automation thermistor, input 0÷120 °C output 4-20 mA.
What is a DAT 4235 170321?
The DAT4235 170321 has an input for an NTC 10k Eliwell temperature sensor, range -10 to 100 °C and the output is 4-20 mA.

DAT4135 Custom products.

Most of the special products designed for the DAT4135 can be also performed on the DAT4235. Here is a complete list of the custom products for the DAT4135.
What is a DAT 4135 91210?
The DAT4135 91210 has an input for an NTC 20K @ 25 °C beta 3991K thermistor.
What is a DAT 4135 151111?
The DAT4135 151111 has an input for 0-300 uA.
What is a DAT 4135 260612?
The DAT4135 260612 has an input for an NTC 10K @ 25 °C PT-43C Beta: 3970 thermistor.
What is a DAT 4135 170713?
The DAT4135 170713 has an input for an NTC 20K selco products curve “C” -5 to 105°C thermistor with an output of 4 to 20 mA.
What is a DAT 4135 270214?
The DAT4135 270214 has an input for Pt100 4wire RTD with a range of -258 to +100°C and an output of 0-10V.
What is a DAT 4135 270514?
The DAT4135 270514 has an input for an NTC Ford 0-100 °C thermistor.
What is a DAT 4135 170614?
The DAT4135 170614 has an input for an NTC 0-60 °C Table B thermistor.
What is a DAT 4135 310715?
The DAT4135 310715 has an input for an NTC beta 2252 thermistor.
What is a DAT 4135 191115?
The DAT4135 191115 has an input for an NTC 49k 15°C to 150°C thermistor.
What is a DAT 4135 230216?
The DAT4135 230216 has an input for an NTC pt25e2 thermistor.
What is a DAT 4135 250216?
The DAT4135 250216 has an input for an NTC USP7766 0-100°C thermistor.
What is a DAT 4135 300516?
The DAT4135 300516 has an input for an NTC Honeywell 100-250°C output 4-20 mA thermistor.
What is a DAT 4135 150616?
The DAT4135 150616 has an input for an NTC Vishay 0-150°C thermistor with an output of 0-10 V.
What is a DAT 4135 160616?
The DAT4135 160616 has an input for an NTC Infineon 0-150°C thermistor with an output of 0-10 V.
What is a DAT 4135 110117?
The DAT4135 110117 has an input for an NTC EPCOS thermistor with a range of 15-100°C.
What is a DAT 4135 150317?
The DAT4135 150317 has an input for an NTC 100 K thermistor with a range of 100 to 180 °C and an output 4-20 mA.
What is a DAT 4135 230617?
The DAT4135 230617 has an input for Tc Ni-NiMo (18%) thermocouple sensor with a range 0 to 1400°C output 4-20mA.
What is a DAT 4135 80218?
The DAT4135 80218 has an input for an NTC 10k Warm up thermistor 0-40°C output 0-10V.
What is a DAT 4135 160218?
The DAT4135 160218 has an input for an NTC 10k Graph thermistor 0-100°C output 0-10V.
What is a DAT 4135 180718?
The DAT4135 180718 has an input for an NTC 10k Maxwell thermistor -5-65°C output 0-10V.
What is a DAT 4135 140119?
The DAT4135 140119 has an input for an NTC -30°C/+220°C thermistor.
What is a DAT 4135 50319?
The DAT4135 50319 has an input for an NTC 10k Cambridge thermistor 0-100°C output 4-20 mA.
What is a DAT 4135 210520?
The DAT4135 210520 has an input for an NTC 92-27-006 thermistor with a range of 0 to 150°C and an output of 4 to 20 mA.
Back to General Description